APC MGE 6739380EN/JC User Manual Page 18

  • Download
  • Add to my manuals
  • Print
  • Page
    / 50
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 17
Page 18 - 6739380EN/JC
7
I
+–
!
!
O
The hidden panel, located behind the
hinged cover, offers the following
indications and control functions:
environment faults;
general faults in system modules;
special control buttons
(see figure 28).
This panel is identical for all types of
cubicles, however, the controls or
indications 8 that do not concern a
given cubicle are not activated.
Clear fault log
This button 10 clears the alarms stored
in memory. The memory may not be
cleared until the cause of the alarms
has ceased.
Buzzer reset
This button 11 stops the buzzer.
A new fault starts the buzzer again.
Battery charge cycle
This button 12 starts a battery charge
cycle (vented lead-acid batteries only).
The cycle duration may be
programmed (default value is 24
hours). Then the RC automatically
shifts to "floating" mode.
Return to float charge
This button 13 can be used during a
charge cycle to force the RC to return
to "floating" mode.
Security button
This button 14 avoids inadvertent
operation of the remaining three control
buttons:
Mains 2 synchronization or
desynchronization;
forced transfer to inverter with load
interruption;
Hidden control panel (Inverter and Static Switch Cubicles)
Fig. 28
forced inverter shutdown with load
interruption;
When pressing one of the above three
buttons, the security button must also
be pressed at the same time.
Mains 2 synchronization or
desynchronization
This button 15 desynchronizes or
resynchronizes the inverter output
frequency with that of Mains 2.
Note:
for parallel-connected modular
UPSs, this function must be carried out
on all the UPSs.
Forced transfer to inverter with load
interruption
This button 16 transfers the load to
the inverter. If the transfer conditions
(Mains 2 characteristics outside
tolerances) are not correct, the transfer
will result in a 0.8 second interruption in
the supply of power to the load.
Note:
for parallel-connected modular
UPSs, forced transfer of the load will
not take place if the number of
operating UPSs required by the load is
greater than one;
for parallel UPSs with centralised
SSC, this function is available only on
the SSC.
Forced inverter shutdown with load
interruption
This button 17 :
transfers the load to Mains 2;
shuts down the inverter.
It may be used if the transfer conditions
(Mains 2 characteristics outside
tolerances) are not correct, in which
case the "inverter off" button 7 on the
visible control panel produces no effect;
is disabled on the SSC.
"Inverter off" button
This gray button 7 turns the inverter
off.
press the "inverter off" button 7 for
3 seconds;
if the transfer to Mains 2 conditions
are correct:
the load is transferred without
interrupting to Mains 2,
the inverter shuts down,
the green "load protected" light 5
goes off and the red "load not
protected" light 2 goes on.
if the transfer to Mains 2 conditions
are not correct, the button produces no
effect. A special function on the hidden
panel may be used to force the
transfer.
Caution:
If the transfer is forced, the load will be
subjected to a 0.8 second interruption
in the supply of power.
Note:
for Modular UPSs or parallel UPSs
with SSC, the shutdown of an inverter
may or may not result in the transfer of
the load to Mains 2, depending on
redundancy conditions;
if the transfer to Mains 2 conditions
are not correct or if the system does not
have a Mains 2, the shutdown of a
single inverter will result in the
shutdown of the entire system if there is
no redundancy.
Hidden control panel
NMLKJIHGFEDCBA
12 345
fault
9 10 11 12 13 14 15 16 17
8
Control panel (cont.)
Page view 17
1 2 ... 13 14 15 16 17 18 19 20 21 22 23 ... 49 50

Comments to this Manuals

No comments