Signal transmission
These signals are each transmitted by
two volt-free changeover contacts with
a maximum breaking capacity of 5A
250V.
"overload" signal indicates that an
overload has taken place (Pload >
Pnominal in kVA);
"rectifier/charger function fault"
signal indicates that:
a fault has taken place in the
rectifier/charger module,
Mains 1 input switch Q1 is open;
"inverter function fault" signal
indicates that a fault has taken place in
the inverter module;
"transfer to inverter fault" signal
indicates that the load transfer
conditions from Mains 2 to the inverter
are incorrect;
"transfer to Mains 2 fault" signal
indicates that the transfer to Mains 2
conditions (voltage, frequency or
phase) are incorrect and a forced
transfer will result in a 0.8 second
interruption in the supply of power to
the load;
"rectifier/charger on" signal
indicates the status of the module.
Note:
A Static Switch Cubicle receives only
the following signals:
overload,
transfer to inverter fault,
transfer to Mains 2 fault.