5
I
+–
!
!
O
4
beep...beep...
légend :
off on
5
I
+–
!
!
O
Main operating modes
(1) Except for frequency converters without a
battery
Fig. 11
The voltages depend on the number of
battery cells and the battery
manufacturer. They can be factory set
and are adjustable by the after-sales
support technicians.
An optional electronic board may be
used to continuously measure the
battery temperature and automatically
adjust the voltages.
Parallel UPS systems:
the power drawn by the load is equally
shared between the different UPSs.
Fig. 12
This information is also available via
volt-free changeover contacts for
remote control devices.
In this case, there is a 30 seconds
delay.
Operation with Mains 1 down
(figure 12)
In the event of a Mains 1 failure or
Mains 1 voltage outside specified
tolerance of –10% in amplitude (–15%
optionally), the rectifier-charger stops
and the battery supplies the necessary
backup power to the load via the
inverter. The battery, float-connected
between the rectifier-charger and the
inverter, discharges during this
operating mode.
The green "load protected" light 5 on
the control panel is on.
The user is warned of battery operation
by a buzzer and the orange "load on
battery" light 4 on the control panel.
Note:
In the event of a Mains 1 failure,
frequency converters without a battery
shut down and the load is no longer
supplied.
Normal operation
Mains 1 power is available:
(see figure 11).
The green "load protected" light 5 on
the control panel is on.
The power necessary for the load is
provided by Mains 1 through the
rectifier-charger and the inverter.
The rectifier-charger also supplies the
power to float charge and recharge the
battery (1). The rectifier-charger output
voltage (DC) is regulated for the
different battery types and charging
modes:
vented lead-acid or Ni/Cd batteries:
two different voltages, one for float
charging and one for recharging;
sealed lead-acid batteries: a single
voltage for both charge functions.
mains 1
rectifier-
charger
battery
inverter
load
static switch
mains 2
mains 1
rectifier-
charger
battery
inverter
load
static switch
mains 2
Introduction (cont.)