Frequency converter or multi-bypass
UPS:
the inverter starts and awaits the
start of the other inverters;
when they are all on or enough have
been started to supply the rated load
power, the output switch for each
running line closes and the load is
supplied with power;
red "load not protected" light 2
goes off,
green "load protected" light 5
becomes constant, on the control panel
of each line supplying the load.
Start-up of an inverter
When the rectifier/charger is on:
press the "inverter on" button 6 on
the control panel;
green "load protected" light 5 blinks
for 3 seconds;
Single-unit or modular UPS system:
the inverter starts and if the transfer
to Mains 2 conditions are correct, the
load is supplied by the inverter;
red "load not protected" light 2
goes off,
green "load protected" light 5
becomes constant.
Modular UPS with external
maintenance bypass or parallel UPS
with SSC:
the inverter starts and awaits the
start of the other inverters;
when they are all on or enough have
been started to supply the rated load
power, the output switch for each
running line closes and the load is
supplied with power;
red "load not protected" light 2
goes off,
green "load protected" light 5
remains on, without blinking, on the
control panel of each line supplying the
load and on the control panel of the
Static Switch Cubicle.
Frequency converter without a
battery:
Start-up of the rectifier/charger
automatically leads to start-up of the
inverter.