APC MGE 6739380EN/JC User Manual Page 48

  • Download
  • Add to my manuals
  • Print
  • Page
    / 50
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 47
Page 48 - 6739380EN/JC
Insulating and Mains 1, Mains 2 and load voltage matching transformer
Harmonics filter and power factor improvement
This option, placed on the Mains 1
input upstream from the inverter,
reduces the reinjection of harmonic
currents into the mains. Harmonic
reinjection, produced by the rectifier/
charger, increases distortion on the
mains.
The amount of the increase depends
on the source impedance. The
reduction in distortion reduces the risk
of disturbing other sensitive loads
connected to the mains. The filter can
also increase the power factor
upstream from the inverter.
Three types of filter are available:
uncompensated filter for the
advantages listed above;
compensated filter for the
advantages listed above and to limit the
capacitive current absorbed by the filter
(additional inductance), in the event the
UPS is supplied by an engine generator
set;
phase shift filter, an economical
solution to limit the reinjection of
harmonics on the mains.
This transformer may be used to match
Mains 2 voltage to that of the inverter,
to create galvanic insulation between
the load and the Mains or to create the
appropriate neutral system.
Options (cont.)
The "Vision" display may be installed
in all types of cubicles (UPS or Static
Switch Cubicle).
"Vision" display
"Remote vision" display
The "Vision" display can operate in two
different modes:
mono-cubicle: the "Vision" display
monitors only the cubicle in which it is
installed;
multi-cubicle: "Vision" display can
monitor all system cubicles (up to eight
maximum). In this mode, the system is
equipped with only one "Vision" display
which may be installed in any of the
cubicles.
Installed in a special enclosure, the
"Remote vision" display provides the
user with remote indications on system
status.
MGE GALAXY 6000 400 kVA
SALLE IQ
Load protected
125 kVA
120%
100%
50%
80%
0
0 Hour 50 Min.
100%
50%
0
Available Backup Time Load level
Normal AC
Bypass AC
Load
equipment
Q1 Q5N
QF1
Q4S
Q3BP
15:24:32 30/05/2005
Home
Alarms
Online
Trend
Statistics
Rectifier
Battery
Inverter
Bypass
Output
Set up
MGE GALAXY 6000 400 kVA
SALLE IQ
Load protected
125 kVA
120%
100%
50%
80%
0
0 Hour 50 Min.
100%
50%
0
Available Backup Time Load level
Normal AC
Bypass AC
Load
equipment
Q1 Q5N
QF1
Q4S
Q3BP
15:24:32 30/05/2005
Home
Alarms
Online
Trend
Statistics
Rectifier
Battery
Inverter
Bypass
Output
Set up
Page view 47