Page 8 - 6739380EN/JC
Isolation and protection devices
Example of a single-unit UPS or single modular UPS
Fig. 8
Fig. 9
Static Switch Cubicle
(figure 9)
Q4S (switch):
isolation of the static switch (and
mechanical contactor K2S) from
Mains 2;
Q3BP (switch):
bypass switch for maintenance;
Q5N (switch):
isolation of the load from the parallel
UPSs;
Q1 (fuse switch):
protection of the cubicle control
electronics from the parallel-connected
inverter outputs;
Q2 (fuse switch):
protection of the cubicle control
electronics from Mains 2.
UPS or converter cubicles
(figure 8)
Q1 (switch):
isolation from Mains 1,
RC start-up;
QF1 (circuit breaker):
battery protection and isolation;
Q5N (switch):
isolation of the inverter, frequency
converter or static switch module from
the load;
Q4S (switch):
isolation of the static switch from
Mains 2;
Q3BP (switch):
bypass switch for maintenance;
FU1-2-3 (fuses):
protection of the RC from Mains 1;
FU5-6-7 (fuses):
protection of the inverter from the
load.
Note:
switches Q4S and Q3BP do not exist
on frequency converters,
circuit breaker QF1 does not exist on
frequency converters without a battery.
External maintenance bypass
cubicle (figure 10)
Q3BP (switch):
bypass switch for maintenance;
Q5N (switch):
isolation of the load from the parallel-
connected UPSs.
Fig. 10
mains 1
load
rectifier-
charger
battery
inverter
static switch
mains 2
Q1
Q5N
QF1
FU1-2-3 FU5-6-7
Q3BP
Q4S
parallel
UPSs
load
static switch
mains 2
Q1
Q5N
Q3BP
Q4S
control
electronics
Q2
Q5N
Q3BP
parallel
modular UPSs
load
maintenance
bypass line