APC MGE 6739380EN/JC User Manual Page 34

  • Download
  • Add to my manuals
  • Print
  • Page
    / 50
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 33
Page 34 - 6739380EN/JC
Visual check
clean the system regularly,
particularly the air inlet and outlet grills.
Check that the air circulates freely in
the cubicles. Use a vacuum cleaner if
necessary;
check that nothing hinders the
ventilation at the top of the system;
check that all the fans operate
correctly.
Functional check
inverter on, open input switch Q1.
The orange "battery" light on the control
panel should light. After two minutes on
battery power, close input switch Q1.
The rectifier/charger should
automatically restart and the orange
"battery" light on the control panel
should go off;
in parallel systems, run these tests
on each UPS or converter.
after-sales support technicians will
power down the system prior to any
maintenance operations.
Note:
In redundant, parallel UPS systems and
frequency converters, the check may
be carried out successively on each
UPS or converter without interrupting
the load. In other configurations and for
the Static Switch Cubicle, the load must
be supplied via the maintenance
bypass (see the "Alarm" section).
check that lights J, K, M and N on the
hidden control panel are not on to avoid
an interruption in the supply of power to
the load due to incorrect transfer
conditions or a battery problem;
press the "inverter off" button and
check that the buzzer and control panel
lights function correctly (see the "main
operating modes" section);
press the "inverter on" button and
check again that the control panel lights
function correctly;
run a transfer to battery test. With the
Autodiagnostics
Note the indications supplied on the
hidden control panel (lights A to
N 8 ).
See the "control panel" section.
In systems with one or several
alphanumeric displays, check the list of
alarms.
If there is a true malfunction, note the
indications and alarms and call the
after-sales support department.