37EcoBreeze System Operation and Maintenance
AFC ModBus Communication
Error
Critical Check ModBus cable between AFC master sensor and
EcoBreeze frame controller.
Power or Sensor failure of AFC master sensor.
For assistance, contact Schneider Electric Customer
Support.
Insufficient Airflow Warning Ensure plenums are clear of obstructions.
Ensure air ports on AFC are clear of obstructions.
Ensure sufficient cooling capacity exists for the load.
For assistance, contact Schneider Electric Customer
Support.
Data Center Airflow Control
Differential Pressure High/Low
Warning The pressure differential at the sensor is outside of the
defined range. Verify that the sensor is functioning
properly.
Verify that the air intake is not obstructed.
Check the tubes, sensor, sensor configuration, and
wiring.
Replace the field installed sensor.
COMMUNICATION ALARMS
Module #[1…N] Not
Responding
Critical Module N (Number) Not Responding.
Check the wiring and CAN connections.
Remove power from then restore power to the Module.
Replace the controller if necessary.
UI Expansion IO Not
Responding
Critical Check the wiring and CAN connections.
Replace the expansion IO Module if necessary.
MIM Fault Critical Check the wiring.
Reboot the controller, check the ERR LED for fault
codes.
Consult the controller documentation for additional
troubleshooting and diagnosis.
Download new firmware.
Repair or replace the MIM controller.
RIM Fault Critical Check the wiring.
Reboot the controller, check the ERR LED for fault
codes.
Consult the controller documentation for additional
troubleshooting and diagnosis.
Download new firmware.
Repair or replace the RIM controller.
Module # [1…N] Inoperable Critical Identify and correct the fault at the Module.
WATER SYSTEM ALARMS
Supply Basin Water
Conductivity High
Warning The water conductivity at the sensor is outside of the
defined range. If the sensor is functioning properly, the
conductivity of the water must be addressed.
Calibrate the conductivity sensors.
Verify the drain solenoid valve is operating properly.
Check the wiring.
• Replace the water conductivity sensor or drain solenoid
valve actuator if needed.
See the Water System manual for more information.
Water Treatment System
Maintenance Required
Warning Specified maintenance should be performed at this time.
Resetting of the maintenance alarm should only be done
by the service technician after maintenance has been
performed.