  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 44
39EcoBreeze System Operation and Maintenance
Ambient Temperature Sensor
Fault, RIM (Frame redundant
controller)
Critical Check the wiring.
Check and clean the sensor.
Check the sensor calibration.
Replace the sensor if needed.
Ambient Humidity Sensor Fault,
MIM (Frame master controller)
Warning Check the wiring.
Check and clean the sensor.
Check the sensor calibration.
Replace the sensor if needed.
Ambient Humidity Sensor Fault,
RIM (Frame redundant
controller)
Warning Check the wiring.
Check and clean the sensor.
Check the sensor calibration.
Replace the sensor if needed.
High Return Temperature Warning Verify the sensor(s) readings.
Check the wiring.
Check and clean the sensor.
Check the sensor calibration.
Replace the sensor(s) if necessary.
Low Return Temperature Warning Verify the sensor(s) readings.
Check the wiring.
Check and clean the sensor.
Check the sensor calibration.
Replace the sensor(s) if necessary.
High Supply Temperature Warning Verify the sensor(s) readings.
Check the wiring.
Check and clean the sensor.
Check for other alarms and failure modes.
Check the sensor calibration.
Replace sensors as necessary.
Low Supply Temperature Warning Verify the sensor(s) readings.
Check the wiring.
Check and clean the sensor.
Check the sensor calibration.
Replace the sensor if necessary.
MISCELLANEOUS ALARMS
Motorized Damper Fault Critical (This is an Optional assembly.) If installed, the alarm is
asserted if the air isolation damper has not been opened/
closed in two minutes after commanded to open/close.
Verify that the damper is not obstructed.
Check the wiring.
Service the damper.
Replace the (field installed) actuator if needed.
Differential Pressure Sensor
Fault
Critical Check the wiring.
• Ensure that the sensor tubing is connected properly and
the tubing is not damaged.
Check the sensor calibration.
Replace the sensor if needed.
Conductivity Sensor Fault
MIM/RIM (Frame master and
redundant controllers)
Warning The conductivity sensor not is functioning properly,
Check the wiring.
Replace the sensor if needed.
Module # [1…N] DX Not
Available
Critical Identify and correct the DX fault within the Module.
Conductivity Sensors not
Calibrated
Warning Service and calibrate the conductivity sensors.
Consult the documentation for the conductivity
transmitter for additional troubleshooting and diagnosis.