APC ACECFR20200SE4 Installation Manual Page 56

  • Download
  • Add to my manuals
  • Print
  • Page
    / 60
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 55
EcoBreeze System Operation and Maintenance50
Quarterly Preventive Maintenance
* Perform all the Monthly Preventive Maintenance items and the items below.
Prepared By: _________________________________
Model Number: _______________________________
Serial Number: _______________________________
Date: ______________________________________
Mechanical
Functional tests
Check the condition of the trough and basin water level sensors. Check and record the outdoor
air temperature and humidity sensor readings.
Verify that the quarterly basin water sample has been taken and sent to a qualified lab for
biological testing (including Legionella).
Check the wiring in the frame electrical panels. Check for loose connections, hardware, and
components.
Measure and record indoor and outdoor fan amperages.
Inspect the supply and return air ducts. Ensure the ducts are open. Check for gaps or air leaks
on outdoor ducts.
Clean or replace the air filters.
Measure and record suction and discharge pressure and temperature sensor readings.
Verify the DX cooling operation mode is functioning properly.
Check condition of inlet water screen, remove, and clean.
Check and clean the outdoor air fan inlet screen.