InRoom CW/DX – Operating Instructions
Maximum equivalent
pipe length = 200 Ft.
approximately
5-6 m (16-20 ft)
3 ft
1 m
3 ft
1 m
max. 5 m (16 ft)
40
Incorrect
Routing refrigerant lines
when the condenser is higher
than the compressor.
Use oil separator for rising
pipe longer than 25 m (80 ft).
For height differences of
over 5 m (16 ft) the system
must be designed so as to
guarantee ad di tio nal sub-
cooling (consult specialist).
Sketch 2 - Dealing with obstacles
Correct
Mounting the refrigerant
pipes in corners
gas
gas
liquid
liquid
Instructions for the routing of refrigerant-conducting pipes
Sketch 1
Sketch 3
Sketch 4