APC INROOM ACPSC3000 Operations Instructions Page 59

  • Download
  • Add to my manuals
  • Print
  • Page
    / 80
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 58
InRoom CW/DX – Operating Instructions
1 2 3 4
ON
OFF
1 2 3 4
ON
OFF
1 2 3 4
ON
OFF
5 6
ON
OFF
5 6
ON
OFF
5 6
ON
OFF
5 6
ON
OFF
7 8
ON
OFF
7 8
ON
OFF
7 8
ON
OFF
7 8
ON
OFF
59
DIP-switch B2-8: Auxiliary functions and automatic drain timings
DIP B2: automatic drainage with electrodes receiving power/not receiving power
ON: electrodes receiving power during automatic drainage
OFF (default): elctrodes not receiving power
DIP B3: automatic drainage when request is reduced by at least 25%
ON: new humidifi cation capacity achieved by steam cycles
OFF (default):
1. new humidifi cation capacity is achieved by steam cycles, if the request
is reduced by less than 25%
2. automatic drainage, if the request is reduced by at least 25%
DIP B4: disabling of the pre-alarm and the wornout cylinder warning (see alarm
table 2 on pages 63 and 64)
ON: warnings are never displayed
OFF (default): warnings are displayed when the cylinder is worn out
time = default
time = default - 30%
time = default + 33%
time = default + 66%
frequency = default
frequency = default - 30%
frequency = default + 33%
frequency = default + 66%
DIP B5-6: DIP B7-8:
automatic drainage time drainage frequency
Caution:
Change the default adjustment only only if APC customer support directs you to do so.
The DIP switches adapt the drain cycle to extreme water conditions beyond the previously
described limit values.