User Manual 990-9178A
DC MX06 40A Shelf Page 11 of 44 18
th
FEB 02
2.1.3 System Output
Output Voltage Nominal
54.5Vdc
V
oltage Adjustment Range
44 V – 57 V (Below 42V LVD contact opens)
Current Rating
42 A @ 230Vac, 36 A @ 115Vac, 28A @ 100Vac
Temperature Coefficien
t
-76mV/°C ±10% (over range 0°C - 50°C)
Current Limi
t
100% - 110% of Rated Current
Reverse Quiescent Curren
t
Less than 100mA, Typically 50mA
Regulation
250mV max for any line or load condition
Over voltage
59.5V ± 0.5V (reset by interruption of AC Input)
2.1.4 Environmental
Temperature Range
-25°C to 50°C operating range
Humidity
85% non condensing
2.1.5 Safety Approvals
Approved to the following
CE marked to the European Low Voltage
Directive 73/23/EEC amended by 93/68/EEC
complies with BS EN60950:2000
Certified to CAN/CSA 22.2#950-00 (NRTL/C
UL1950 3rd Edition)
2.2 Display + LED’s
3½ Digit LED Displa
Switchable between “Volts” and “Amps”
“Volts”
System Output Voltage
“Amps”
Total Output Load Current
Load Current = Rectifier Current – Batt Charge Current
4 LED Rectifie
r
Input Healthy
G
reen
Output Healthy
G
reen
Current Limit Red
Overvoltage Red
Single LED Rectifie
r
Rectifier Fail Red
Alarm Card LED’s
Input Fail Red
Distribution Trip Red
Major Fault Red
Minor Fault
Y
ellow
NB/ LED’s are lit when description is true.