User Manual 990-9178A
DC MX06 40A Shelf Page 32 of 44 18
th
FEB 02
4.2 DC Distribution
The MX06 40A Shelf has a DC distribution module fitted. This module contains the chosen distribution
components of either circuit breakers or fuses. It also contains an LVD contact (controlled by the controller)
and a current shunt measuring load current. The modules can be configured for either positive or negative
earthed output. The output can also be left floating to facilitate external grounding. A tripped output will give
an alarm displayed as a front panel LED.
There are three standard distribution component types:
1/ 10 GMT Fuses
2/ 4 Cartridge Fuses
3/ 4 Circuit Breakers
As explained earlier all three types are offered with either front or rear cable access giving six modules
types.
4.2.1 10 GMT Fuses Rear Access
No. of Outputs :
10 max
Output Rating :
10A max per output
(42A total)
Fuses :
GMT-** (Bussmann)
Trip Alarm :
YES
• Cables should be rated to at least the same
current rating as the corresponding output fuse
and be colour coded as to meet all the local
installation regulations.
• To attach the cables remove the rear cover fo
access to output connectors.
• Simply strip the ends of the cables and screw into
output terminal block.
Output 1
Distributed Output 1
Distributed Output 10
Output 10
Top Connector :
Common (0V Return) / Earth (if link fitted)
Bottom Connector :
- 54Vdc (when positive earthed)
DISTRIBUTION
FUSES
1
2
3
4
5
6
7
8
9
10