Page view 16
6739381EN/
160kVA to 400kVA modular UPS rectifier-inverter cubicle
cross-section AA
front view
Cables connect by lugs:
mains 1, mains 2 and load:
to 40 X 4 mm copper terminals and
13 mm diameter holes;
battery:
250 to 300 kVA UPSs:
to 65 X 4 mm copper terminals and
13 mm diameter holes,
400 kVA UPSs: to 80 X 5 mm copper
terminals and 13 mm diameter holes.
Height of connections relative to floor:
mains 1, mains 2 and load: 440 mm;
battery: 390 mm;
remote relay board: 1030 mm.
600 kVA single-unit UPS cubicles (see the appendix).
A
rectifier
charger
inverter
stack
inverter
stack
A
additional remote relay board
(optional)
L1L2 L3
mains 1
L+ L
battery
L1L2 L3N
load
static
switch
inverter
stack
XR7
XR6
XR5
XR9
XR8
XR3
XR4
card
cage
XR2
XR1
remote relay
board
L1L2 L3N
spacing
uprights
spacing
uprights
cable
tie bar
air extraction
air admission
air admission
transformer
connection
from below
trough (if applicable)
rear
front
card
cage
mains 1,
mains 2,
load
battery
cable tie bar
power cable routing
via the bottom
mains 2
Q1
Q5NQ3BP
Q4S
off
on
off
on
off
on
off
on
APOZ board
MISI board
XM7
XM5
XM6
XM136
XM137
XM12
XM10
XM11
INTZ
board
FHCZ
board