APC MGETM GALAXYTM 6000 User Manual Page 7

  • Download
  • Add to my manuals
  • Print
  • Page
    / 46
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 6
6739381EN/
Electrical parameters for determining cable cross-sections
the battery current values and cable
cross-sections have been determined
for a battery at the end of a charge
cycle;
the current values and cable sections
for Mains 2 and load are given for full
rated load with a power factor of 0.8.
Parameters for single-unit UPS cables
line currents absorbed in Amps cross-sectional area of Cu cables in mm
2
(2)
Mains 1 415V battery Mains 1 415V battery
with or without
Mains 2 with or without battery Mains 2 and load
battery (1)
and load Copper Aluminium Copper Aluminium Copper Aluminium
250 407 361 630 185 300 150 240 240 2 x 185
300 490 433 758 240 2 x 150 240 2 x 150 240 2 x 240
400 654 577 1013 2 X 185 2 x 300 2 x 150 2 x 240 2 x 185 3 x 185
450 735 649 1137 2 X 185 2 X 300 2 X 185 2 x 300 2 x 185 2 x 300
500 821 722 1252 2 x 240 4 x 185 2 X 185 2 x 300 3 x 150 3 x 240
600 981 866 1519 3 x 240 4 x 240 2 X 240 4 x 185 3 x 185 2 x 400
rated
inverter
output
in kVA
(1) the rated Mains 1 currents (In) have been
determined for a minimum float charging voltage of
423V and full rated load with a power factor of 0.8.
(2) the cable cross-sections are given for copper
conductors. They are calculated according to
permissible temperature rise and allow for line
voltage drops over a maximum length of 100 m
(AC circuits) or 25 m (DC circuits if cables not
provided). For greater lengths, the cross-sections
should be chosen to limit voltage drops to 3% (AC)
or 1% (DC).
this table has been drawn up for
rated phase-to-phase Mains and load
voltages of 415V. For voltages of 380V,
multiply the currents for Mains 2 and
load by 1.09; for voltages of 400V, use
the table in another language version of
this manual;
the current values and cable cross-
sections for Mains 1 are given for full
rated load with a power factor of 0.8
and a battery consuming its minimum
float charging voltage;
For frequency converters, the
parameters concerning Mains 2 are not
applicable.
The load parameters common to all the
converters are given in the table below.
For a parallel UPS, the parameters for
Mains 2 and load are also provided in
the table below.
For a modular UPS, the parameters
for Mains 2 and load are also
provided in the table below.
Characteristics (cont.)
NF C 15-100 authorizes a maximum of 4
cables per phase.
Heat losses
rectifier-inverter cubicles
rated heat
inverter losses (1)
output
in kVA in kW in cal./s
250 13,5 3220
300 17,5 4170
400 23 5480
450 25 5960
500 30 7150
600 32,8 7830
(1) the indicated heat losses are those produced
by the unit at full rated load and with the battery
float charging. They must be taken into account
when dimensioning the air conditioning system.
The cubicles are cooled by forced ventilation.
The air enters via the doors and grids at the bottom
and is discharged via the roof.
static switch cubicles
rated heat
SSC losses (1)
output
in kVA in kW in cal./s
500 2,9 696
800 3,7 888
1200 < 0,5 < 120
2000 < 0,5 < 120
(1) the indicated heat losses are those produced
by the unit at full rated load when operating on
Mains 2. They are not to be taken into account
when dimensioning the air conditioning system.
The cubicles are cooled by forced ventilation.
"Pack advance" cubicles
rated heat
inverter losses (1)
output
in kVA in kW in cal./s
300 2,2 525
400 2,6 620
450 2,6 620
(1) the indicated heat losses are those produced
by the unit at full rated load and with the battery
float charging. They must be taken into account
when dimensioning the air conditioning system.
The cubicles are cooled by forced ventilation.
The air enters via the doors and grids at the bottom
and is discharged via the roof.
Page view 6
1 2 3 4 5 6 7 8 9 10 11 12 ... 45 46

Comments to this Manuals

No comments