23EcoBreeze System Operation and Maintenance
Reset (Option) Run Hours
Enter Yes to confirm
ESC to exit
Yes/No
No will be in the highlighted box on the screen. Press
ENTER to cause the box to flash. Then
press the
UP key to change the No to Yes. Press ENTER to save your change. Press ESC to
return to the option selection screen.
Path: Main > Configure Frame
Air Controls. (Requires device password)
Setpoints
– Supply Air: 20°C - 32.2°C (68 - 90°F)
– Containment: 100.0 Pa (0.4” WC)
Fan Speed: 20% - The speed of the IT fans. This setting only applies when IT Fan Mode
is set to Manual (see “Air Setup” on page 24).
The Supply Air setting is in the highlighted box when the screen opens. Move the highlight box
down the list to select the setting and press
ENTER to select it. The box will start to flash. Use
the
UP or DOWN key to change the setting. Press ENTER to save the setting. Press the DOWN key
to select another setting to adjust or press
ESC to go back to the Configure Frame screen.