EcoBreeze System Operation and Maintenance24
Water Controls. (Requires device password)
Lead Pump: A or B
Pri Water Src: A or B
Drain Basin: Basin Draining - When this menu item is selected, if the Frame is off
(Operate = Off), the basin will be drained.
Use the
UP or DOWN keys to move the highlight box to your selection and press ENTER to select
it. The box will start to flash. Use the
UP or DOWN arrows to change the setting. Press ENTER to
save the setting. If you select Drain Basin, when
ENTER is pressed, the confirmation screen
opens.
Enter Yes to confirm
ESC to exit
Yes/No
No will be in the highlighted box on the screen. Press
ENTER to cause the box to flash. Then
press the
UP arrow to change the No to Yes. Press ENTER to save your change. Press ESC to
return to the option selection screen.
Air Setup. (Requires admin password):
IT Fan Mode:
AUTO: Air flow is automatically controlled by the unit via a user tuned PID. This
requires that a user supplied differential pressure sensor be connected to the remote
interface panel and configured via the DP Sensor Sel, DP Sensor Min and DP Sensor
Max properties or AFC is attached to the EcoBreeze.
– Manual: The air flow is fixed to the value of the Fan Speed property (see “Air
Controls” on page 23).
– Elevation: -46 - 914 m x 10 (-150 - 3000 ft x 10): Elevation above sea level. This is
important for the EcoBreeze controller to be able to accurately estimate coil
performance.
Damper Present: No/Yes - When set to Yes, the controller will automatically control a
user supplied air isolation damper.
Containment Gain: 0 - 100% /Pa - When the IT Fan Mode is set to Auto, this property is
the proportional multiplier (gain) for the actuator. The proportional multiplier adjusts for
the difference (error) between the measured value and the setpoint.
Containment Reset: 0 - 999/sec - When the IT Fan Mode is set to Auto, this property is
the integral multiplier (reset rate) for this actuator. The integral multiplier adjusts for error
measurement and the amount of time that the error has existed. The integral multiplier
adds to or subtracts from the output in small increments to correct for the offset error
caused by the proportional contribution (0 - 999 sec). Note that setting the Reset to 0
secs will disable reset, effectively making the controller a gain only controller. This mode
can be useful for PID tuning.