4.1.3 3 Phase Star Supply
The MX06 40A Shelf can be used on any of the following supplies: 415V, 400V, 380V or 208V
phase to phase.
The maximum input current is 13A per phase on a 208Vac phase to phase supply and 7.2A per
phase on a 380Vac, 400Vac or 415Vac supply. Choose AC Input cabling rated accordingly and
colour coded as required for country/state concerned.
4.1.3.1 Rear access connection
To connect the input supply to the MX06 40A Shelf proceed as follows:
The AC input current to the system should also be limited by an appropriate device in the
event of a short circuit as defined in EN60950 to protect the internal wiring of the end use
equipment. The device(s) should be rated accordingly.
Ensure that the AC supply intended for connection is isolated, locked off and under single
operator control. Remove the rear cover to leave the view as shown below
The main circuit board should have been configured for 3-phase star use by removal of LK2
and LK3. This is normally factory configured.
First the safety earth connection should be connected to one of the studs labelled below
Connect inputs: Phase 1 to AC1, Phase 2 to AC3, Phase 3 to AC5, Neutral to AC2, 4 or 6
(neutral is required as system is a star configuration)
Connect the cables terminated with M4 ring crimps using the M4 x 8 screws supplied in the
accessory kit.
Cables should exit through the top left knockout tab. If an alternative knockout is to be used
ensure additional insulation is used where cabling passes over secondary parts. Cables
should be routed as close to the top of the shelf using the supplied routing clips (see section
4.3 for further routing details.
Refer to section 5 entitled “Commissioning the system” before applying AC power.
Safety
Earth
AC6
Phase 3
AC5
Phase 2
AC3
AC4 AC2
Safety
Earth
Top Left
LK3
LK2
Phase 1
AC1