User Manual 990-9178A
DC MX06 40A Shelf Page 33 of 44 18
th
FEB 02
4.2.2 10 GMT Fuses Front Access
To connect the cables to the system proceed as follows:
• Cables should be rated to at least the same current rating as the corresponding output fuse
and be colour coded as to meet all the local installation regulations
• Remove the distribution front panel to give easier access to terminal block if required. To
attach the cables simply strip the ends and screw into output terminal block
• Ensure stray wires do not contact the front panel metalwork.
GMT Fuse ratings
No. of Outputs :
10
Output Rating :
10A max per output
(42A total)
Fuses :
GMT-** (Bussmann)
Trip Alarm :
YES
GMT Fuse 1
Bottom Connector :
- 54Vdc, +Ve earth
GMT Fuse 10
Output 10
Output 1
Top Connector :
Common (0V Rtn) / Earth (if
earth link fitted)
Output 10
Output 1
INPUT DISTRIBUTION CONTROLLER
FUSES
1
2
3
4
5
6
7
8
9
10
Ambient Temperature
20
o
C 50
o
C 65
o
C
10A 7A 6A 5A
12A 8A 7A 6A
Continuous
Current Ratin
15A 10A 9A 8A
This table shows that the continuous curren
rating of a GMT fuse is less than the specified
current rating. It also shows that it is affected
by ambient temperature.
Lower value fuses follow the same pattern.