Start-Up Procedure
34 150 kW InfraStruXure Power Distribution Unit
3. Open (turn OFF) the main output breaker on the front of the PDU.
Apply power to the system
1. Close (turn ON) the main circuit breaker for the power source feeding the PDU.
2. Close (turn ON) the main input breaker on the PDU.
3. Verify that the proper voltage is present on the secondary winding of the transformer (208 V,
metered phase-to-phase) using a true RMS voltmeter.