SURT15k/20k 230 VAC Stack/Rack-Mount 6U XLI/XLICH/XLI-CC 25
Maintenance
Replace battery modules
This UPS has easy-to-replace, hot-swappable battery modules. Replacement is a safe procedure, isolated from
electrical hazards. You may leave the UPS and connected equipment on during the replacement procedure.
Once the batteries are disconnected the connected equipment is not protected from power outages.
Refer to the appropriate replacement battery user manual for battery module installation instructions. See your
dealer or contact APC at www.apc.com for information on replacement battery modules.
General Fault Fan Fault A fan has failed. Contact APC Customer Support. Refer
to Contact Information in this manual.
Static Bypass Switch Fault. The static bypass switch has failed.
System Failure Detected by
Surveillance.
The system has detected an internal error. Check for other alarms.
If the problem persists contact APC
Customer Support. Refer to Contact
Information in this manual.
System Not Synchronized
to Bypass.
System cannot synchronize to bypass
mode.Bypass mode may be unavailable.
Option 1) Decrease input frequency
sensitivity.
Contact APC Customer Support. Refer
to Contact Information in this manual.
Option 2) Correct bypass input voltage
to provide acceptable frequency or
voltage.
UPS In Bypass Due To
Fault.
The UPS has transferred to bypass mode
due to a fault.
Contact APC Customer Support. Refer
to Contact Information in this manual.
UPS In Bypass Due To
Overload.
The load has exceeded the power
capacity.
Decrease the load.
UPS Is Overloaded. The load has exceeded the system power
capacity.
Option 1) Decrease the load.
Option 2) Check the load distribution on
the three phases through the PowerView
display. If the load is unevenly
distributed, adjust the load distribution.
Be sure to deliver the spent battery(s) to a recycling facility or ship it to APC in the replacement
battery packing material.
Condition
PowerView Display
Message Reason for Message Corrective Action