SURT15k/20k 230 VAC Stack/Rack-Mount 6U XLI/XLICH/XLI-CC 5
Mount units in rack
The UPS and XLBP should be installed at or near the bottom of the rack. Always place the UPS above the
XLBP(s). Batteries must be removed from the XLBP(s) prior to installing the unit(s) in a rack. Refer to the
instructions on the packaging for details on removing the batteries from the XLBP.
Install units in rack
Secure the UPS and the XLBP in the rack
using the cage nuts and ornamental screws
included in the package.
Four ornamental screws and two cage nuts
must be used to secure each unit.
A cage nut must be used in the top hole of each
rack-mount bracket when securing the unit in
the rack.
The bottom hole of each rack-mount bracket
must be secured using an ornamental screw in
the threaded hole.
Install and connect battery modules
Connect all eight battery modules. Failure
to do so may cause equipment damage.
Replace the battery doors.
Tighten the screws to secure the battery doors.