Mass Configuration: Sensor and Alert Settings
InfraStruXure Central 4.0 User’s Reference 115
method-specific instructions, see “Creating Alert Actions” on page 221.
5. Click OK to save this new Alert Action for use with all selected devices.
Once you have saved the Alert Action it will appear in the list of defined Alert Actions for the selected
devices and will be available for use in the Alert Profiles task.
Editing Previously Defined Alert Actions
To edit a previously defined alert action:
1. Launch the Alert Actions task.
2. Select the alert notification-specific tab that corresponds to the type of alert action you want to
create. Any selected devices that have previously been configured with an alert action that uses the
selected alert notification method are displayed in the pane.
3. Select one or more devices and then click Edit.
4. Specify the new notification information for this Alert Action. The information that must be
provided for an Alert Action depends on which alert notification method you have selected. For
detailed notification method-specific instructions, see “Creating Alert Actions” on page 221.
5. Click OK to save this updated Alert Action for use with all selected devices.
Alert Profile
Use the Alert Profile task to customize alert notification policy used by your devices. You can customize
your device’s default alert notification policy, or create additional alert notification policies to simplify
alert management. You can also use the Alert Profile task to temporarily disable all alert notifications
globally associated with an Alert Profile.
The alert policy defines the notification actions that are taken by the device in response to alert
conditions. The alert profile consists of one or more alert sequences. An alert sequence specifies:
The period of time that must pass before an alert condition results in notification.
The number of times the notification will be repeated if the alert condition goes uncorrected.
The time interval at which the notification is enacted
One or more Alert Actions that are taken as part of the Alert Sequence's notification process
The schedule that determines whether the Alert Sequence is active at the date and time that the alert
occurs
Capture settings that can be used to override specific alert-action attributes, such as including
graphs or image captures with alert notifications
For more information about alert sequences, see “Creating an Alert Sequence” on page 116.
The Default Alert Profile
APC NetBotz appliances come pre-configured with a Default Alert Profile. This Default policy features
the following 4 pre-configured Alert Sequences, all of which are scheduled to be active 24 hours a day, 7
days a week:
Alert Level 1: Begins immediately after an alert condition occurs (Start Value of 0), repeats 2 times
at a 5 minute interval. Initiates the following pre-defined Alert Actions: Primary E-Mail
Notification, HTTP Post, FTP Data Delivery.