Mass Configuration: Sensor and Alert Settings
InfraStruXure Central 4.0 User’s Reference 141
list.
3. Select the desired threshold operation and targets:
If you are editing one or more previously defined below value for time thresholds, select the
devices on which the threshold has been configured from the Management Devices list and then
click Edit.
If you are defining a new below value for time threshold click Add. Then, select one or more
devices for which this threshold will be configured, and click Next. Finally, select the sensors on
the selected devices for which this threshold will be configured and then click Next.
4. Type in the Threshold Name field a name for this threshold.
5. Specify Basic threshold settings. From the Basic tab in the Thresholds pane:
a. Type in the Minimum field (or use the arrows in the field to specify) the highest acceptable value
for the selected sensors. This is the value that, if fallen below for greater than the number of
seconds specified in the Time Allowed Below Minimum field, will result in an alert condition.
b. Type in the Time Allowed Below Minimum field (or use the arrows in the field to specify) the
number of seconds that the reported value can fall below the value specified in the Minimum
field before an alert condition is generated.
c. Check the Enabled check box to enable the threshold. If this check box is not checked, the alert
threshold will be saved but will not be active.
Add to the Threshold-Specific Addresses list the e-mail addresses of any personnel to whom e-
mail alert notifications should be sent if this threshold triggers an alert condition. Click Add...,
type in the e-mail address to which the alert notification will be sent, and then click OK.
If you’ve installed an SMS-capable modem you can deliver alert notification to SMS-enabled
devices by entering threshold-specific addresses for them in the following format:
sms:sms_device_address
where sms_device_address is the telephone number or e-mail address associated with the SMS-
enabled device (for example, “sms:5123334444” or “sms:[email protected]”).
6. If desired, specify Advanced Threshold settings. All Advanced threshold settings are optional. From
the Advanced tab in the Thresholds pane:
Specify a Return To Normal Delay value. Use the controls to specify the number of seconds that
must pass after this threshold has returned to normal before the threshold state is considered
returned to normal. Default value is 0 (state returns to normal immediately after the measured
value is no longer violating the threshold).
Set an Advanced Schedule for this threshold (optional). By default, all thresholds are assumed to
be enabled 24 hours a day, 7 days a week. However, you can specify that a threshold will be
enabled only during specific time ranges. To set an Advanced Schedule:
a.Click Advanced Schedule.... The Schedule Threshold window opens.
b.By default, all time periods in the schedule are set to Enabled. To disable the threshold for a
currently enabled period of time, highlight the period of time by clicking-and-dragging over the
Note
These threshold-specific notifications are sent only if your device has one or more Alert
Actions defined that use the Send E-Mail Message alert notification method and that have
the Include Addresses from Thresholds check box checked. For more information, see
“Alert Actions” on page 113 and “Creating Alert Actions” on page 221.