Surveillance View
266 InfraStruXure Central 4.0 User’s Reference
If the selected device support motion or block out masking, then additional panes will be available that
enable you to configure these settings on the selected device.
Note: The Send On Motion Detected and Send On Motion Detected During Alerts modes are available on
all Surveillance-licensed NetBotz devices, regardless of whether the Camera Motion Sensor license key
is installed or not.
1. Use the controls in the Surveillance Activation Settings window to configure the surveillance
settings for the selected devices.
2. Set Advanced Surveillance Sensor Settings (optional). Click Advanced.... Use the Advanced
Surveillance Sensor Settings to enable and disable Surveillance on the selected device for user-
specified time ranges.
By default, if you license a device for Surveillance use then that device gathers surveillance data 24
hours a day, 7 days a week. However, depending on the location in which you have installed your
APC NetBotz device and the manner in which you plan to use it you might not want surveillance to
be active all of the time. Use the Advanced Surveillance Sensor Settings to define specific time
periods when Surveillance is Enabled or Disabled on the device. Then, if a condition occurs during
a period when the sensor is disabled that would ordinarily cause surveillance data to be generated
the condition will be ignored.
To use the Advanced Surveillance Sensor Settings task to disable a surveillance for a specified
period of time:
a. Click on a timer range in the Enabled/<Disabled> Time selection list that includes the period of
time during which you want surveillance to be enabled or disabled. For example, if you want to
disable surveillance from 8:00AM until 6:00PM on Wednesdays, click on the entry in the
Enabled/<Disabled> Time selection list that includes that time period. By default there is one 24-
hour “Enabled” entry for each day defined for each sensor, so if you have not previously set up an
Advanced Sensor Setting on this device you would select Wednesday 12:00AM - 12:00PM.
b. Use the drop-boxes in the Time Interval group to select a new time range to disable Surveillance.
Then click Disable to update the Enabled/<Disabled> Time selection list to exclude the specified
time range.
c. Click OK to save the Advanced Surveillance Sensor Settings for this sensor and to return to the
sensor settings window.
3. When you are finished configuring the Surveillance settings for selected devices, click OK to save
your settings.
Target image capture rate Specifies the target number of images captured by the device per
second. Note that, depending on image content, network load,
and other factors, the actual number of images captured per send
can be fewer than the specified value.
Event duration trigger (seconds) The minimum number of seconds that must pass before a
Surveillance event will be triggered.
Note
Time periods during which surveillance is enabled are displayed in the Enabled/
<Disabled> Time selection in bold and are colored blue. Time periods during which
surveillance is disabled are displayed in italics and are enclosed by <brackets>.
Field Description
Page view 266