Overview: InfraStruXure 20kW System Components
6 InfraStruXure 20kW SystemInstallation, Operation, and Maintenance
Front view (interior)
42-position circuit breaker
panelEach system has a
circuit breaker panel with 39
pole positions available for load
equipment. Thirty-seven poles
provide power at 120 volts L-N;
two poles provide 208 volts L-L.
The amperage provided by each
position depends on the size of
the circuit breaker used.
Intelligence module —The
main intelligence module (MIM)
is the main controller of the
system. It reports status,
configures the UPS, performs
UPS diagnostics, manages
power and batteries, controls
general UPS performance,
regulates output voltage, and
accommodates power module
load-sharing. The redundant
intelligence module (RIM) is the
redundant controller. The RIM is
identical to the MIM (same part
number), and is responsible for
system operation
if the MIM fails or is removed. When you have two intelligence modules, you can remove one
without affecting the load. However, when you only have one intelligence module, always put the
system in maintenance bypass before removing it.
Power module— Each power module can support up to 10kVA of power. Each time you add a
power module, you increase the total capacity of your UPS. The total capacity cannot go above
20kVA (N+1). You can have up to three power modules in each system and they can be removed
without affecting the load.
Battery module—A battery module consists of four battery units. Battery modules can be removed
without affecting power supplied to the load. The number of battery modules determines the
runtime of a particular load. A battery module provides six minutes of runtime to one power module
at full load (assuming a 0.8 load power factor).
Static switch module—The static switch module is a parallel power path within the system. If the
system suffers a catastrophic failure, the static switch is activated; input power bypasses the power
modules; and power flows through the static switch to the connected load. The static switch has its
own power supply and operates on a fail-safe signal from the intelligence modules. This module
cannot be removed without affecting the load.