Maintenance: Adding Parts
72 InfraStruXure 20kW System: Installation, Operation, and Maintenance
Connect the power cable wires.
1. At the back of the panel:
a. Secure the power cable using the wire ties on the back of the panel.
b. Connect the neutral wire to the closest open termination point on the Neutral Bar (
Q
).
c. Connect the ground wire to the closest open termination point on the Ground Bar (
J
).
d. Route the L1, L2, and L3 wires over (shown) or under the back of the panel.
2. At the front of the panel, connect the L1, L2, and L3 wires to the circuit breaker(s). The
illustration below shows three-pole breakers; however, you can also connect single-pole
breakers.
Q
J