Specifications: InfraStruXure 20kW System
76 InfraStruXure 20kW System: Installation, Operation, and Maintenance
Input
Input Current
Normal 61.3A Current that flows at nominal mains with batteries fully
charged
Maximum 70.9A Current that flows at nominal mains with charging batteries
Limit 89.4A The maximum continuous input current limit that can be
drawn at low mains with charging batteries
Overload 115.0A For 30 seconds. Based on 150% overload on output
Walk-in duration 15s On re-transfer from mains to battery, RMS current will
linearly ramp in for 10 seconds.
Power factor 0.99 At full load
Total harmonic distortion (THD) < 6% At full load
Input Voltagenormal operation
Nominal 208V
Minimum 166V At less than full load, the UPS will operate from mains
power to lower voltages.
Maximum 240V Above 240V, the UPS will operate from battery power.
Input Voltagestatic bypass
Minimum 183V
Maximum 233V
Input Frequency
AC mains input 4070Hz Outside of this range, the UPS will operate from battery
power.
Batteries
Battery type Maintenance-free, sealed, lead-acid battery with suspended electrolyte
leakproof
Battery voltage
Nominal battery voltage ± 192Vdc
Float voltage ± 219Vdc
No boost charge voltage
End of discharge voltage ± 160Vdc May be higher at less than full load.
Temperature compensation –320mV per
°C
For temperatures greater than or
equal to 20°C.
0mV per °C For temperatures less than 20°C.
Battery charging
2kW N system2 power modules (May drop to lower values at
low AC Mains.)
Maximum charging power
3kW N+1 system3 power modules (May drop to lower values
at low AC Mains.)