InfraStruXure 20kW System: Installation, Operation, and Maintenance 47
Procedures
How to transfer the InfraStruXure 20kW System UPS into maintenance
bypass operation
Before servicing the InfraStruXure 20kW System UPS, transfer the UPS into maintenance bypass
operation. When the UPS is operating in maintenance bypass, input power flows directly to the
InfraStruXure 20kW System distribution circuit breaker panel and out to the load equipment.
1. Command the UPS into static bypass operation through the UPS display interface:
a. Press the
E
SC
key at the top-level status screen to
open the top-level menu.
Top-Level Menu
b. Select Control on the top-level menu, and press
the
E
NTER
key.
c. Select UPS Into Bypass on the Control menu
and, press the
E
NTER
key.
Control Menu
d. Confirm the selection on the next screen: select
YES, UPS into Bypass, and press the
E
NTER
key.
Confirmation Screen
The BYPASS LED illuminates and the following screens appear:
Note
The H3 LED above the Q3 switch illuminates, indicating that it is safe to operate
the Q3 switch.
Control
Status
Setup
Accessories
Logging
Display
Diags
Help
UPS Into Bypass
Do Self Test
Simulate Power Fail
Graceful Reboot
Graceful Turn Off
Start Runtime Cal
Turn UPS Output On
Confirm:
UPS into Bypass
Cancel
YES, UPS into Bypass
Bypass attempted
Please wait...
UPS IS BYPASSED
Press any key...