InfraStruXure 20kW System: Installation, Operation, and Maintenance 75
Specifications
InfraStruXure 20kW System
Performance
Efficiency
ACAC at nominal mains 91.5% Minimum from 75% to full load when
configured as 20kVA n+0
DCAC at nominal battery voltage 94% Minimum from 75% to full load when
configured as 20kVA n+0
Electrical
Output
Output Power 20kVA / 20kW
Load power factor 0.5 to 1.0
Output Currentnormal or battery operation
Full load 55.5A
Overload 1 83.3A 150% for 30 seconds
Crest factor 2.7
Output Currentstatic bypass
Overload 1 69.4A 125% continuous
Overload 2 555.1A 1000% for 500ms
Output Voltagenormal or battery operation
Nominal 208V
Minimum 205.9V -1%
Maximum 210.1V +1%
Dynamic load response +/- 5% For load step 0% to 100% or 100% to 0%.
Recovery back to steady state: < 60ms.
Total harmonic distortion (THD) < 2% 100% resistive load
< 6% Computer load as defined by EN50091-3/
IEC 62040-3
Output Frequency
Normal operation Synchronized to bypass input
Frequency is synchronized to mains over the range of 57
to 63Hz. Optional +/- 0.1Hz and +/-10Hz setting from
front panel.
Battery operation 60Hz
Slew rate 1 Hz/s