Specifications: InfraStruXure 20kW System
InfraStruXure 20kW System: Installation, Operation, and Maintenance 79
Communication and Management
Interface port DB-9 RS-232, RJ-45 10 Base-T Ethernet for web/SNMP,
internal modem for out-of-band management
Card slots 2
Management software included PowerChute Symmetra Bundle
Control panel Multi-function LCD status and control console
Audible alarm Alarm when on battery; distinctive low battery alarm; configurable
delays
Emergency Power Off (EPO) Yesprimary wiring (dry contact closure or applied 24Vdc)
Optional Management Devices AP9607: 2-Port Interface Expander
AP9615: 5-Port 10Base-T Hub SmartSlot Card
AP9612TH: Environmental Monitoring SmartSlot Card
AP9610: Relay I/O SmartSlot Card
AP9618: APC Network Management Card
Installation and Wiring
Connection type Input configuration: Allowable output connections:
3P + N + G 3P + N + G or 3P + G
System Mains Input Protection:
UPS Withstand rating 30,000 symmetrical amps RMS
Protection type and rating Condition: The UPS plus the following options:
(External to the UPS) Input Isolation Transformer Protection Type Notes
Present 90A 3 pole breaker
(30k AIC)
1,2,4
Not Present 90A Class J Current
limiting fuse
3,4
Note 1: If available fault current is less than 30kA, a lower AIC rated
breaker may be used.
Note 2: Isolation transformer contains 90A Class J fuse on primary
Note 3: Current limiting fuse is required to limit fault current through
static switch
Note 4: Each power module contains 2 pieces of 30A fuse in parallel on
its input