Troubleshooting: Alarm Messages on the Display Interface
InfraStruXure 20kW System: Installation, Operation, and Maintenance 61
Runtime Is Below Alarm
Threshold
The predicted runtime is lower than
the user-specified minimum runtime
alarm threshold. Either the battery
capacity has decreased, or the load
has increased.
Option 1: Allow the battery modules
to recharge.
Option 2: If possible, increase the
number of battery modules.
Option 3: Reduce the load.
Option 4: Raise alarm threshold.
Load Power Is Above
Alarm Limit
The load has exceeded the user-
specified load alarm threshold.
Option 1: Use the display interface to
raise the alarm threshold.
Option 2: Reduce the load.
Load Is No Longer
Above Alarm Threshold
The load exceeded the alarm
threshold and the situation has been
corrected either because the load
decreased or the threshold was
increased.
No corrective action necessary
Min Runtime Restored The system runtime dropped below
the configured minimum and has been
restored. Additional battery modules
were installed, the existing battery
modules were recharged, the load was
reduced, or the threshold was raised.
No corrective action necessary
Display message Meaning Corrective action