Troubleshooting: Alarm Messages on the Display Interface
InfraStruXure 20kW System: Installation, Operation, and Maintenance 59
Internal Communica-
tions Failed
One of the buses used for the commu-
nication between the Intelligence
Modules failed.
Contact APC Customer Support. See
Customer Support section.
No Working Power Mod-
ules Found
No working Power Modules were
found.
Option 1:
Check that all power mod-
ules are properly inserted, the two fas-
tening screws are tight, and the
locking latches are engaged.
Option 2: Check for other alarm mes-
sages.
XR Frame Fault One of the Battery Frames has failed. Contact APC Customer Support. See
Customer Support section.
System Not Synchro-
nized to AC Line
System cannot synchronize to AC line
and bypass mode may not be available
if required.
Option 1: Decrease the sensitivity to
input frequency (select Startup, Setup,
Output Freq, and select value).
Option 2: Correct the input voltage to
provide acceptable voltage on fre-
quency.
Battery Voltage Is Too
High
The battery voltage is too high and the
charger has been deactivated.
Contact APC Customer Support. See
Customer Support section.
Site Wiring Fault Wrong phase rotation on the input
side.
An electrician should check that the
UPS has been wired properly.
Isolation Transformer
Over-temperature
The Isolation Transformer tempera-
ture is too high.
Contact APC Customer Support. See
Customer Support section.
External DC Disconnect
Switch Tripped
The external DC disconnect switch
tripped. Battery power is not available
or the runtime is lower than expected.
Activate the external DC disconnect
switch.
Sys Power Sply Fail A system power supply has failed.
One of the power supplies has to be
changed.
Contact APC Customer Support. See
Customer Support section.
Battery Monitor Card
Failed
The battery monitor card has failed. Refer to Module Replacement section
for further details.
Battery Monitor Card
Removed
The battery monitor card has been
removed.
If the battery monitor card has not
been removed, check that it has been
properly inserted.
Switch Gear Communi-
cation Card Fail
The switch gear communications card
has failed.
Refer to Module Replacement section
for further details.
Switch Gear Communi-
cation Card Removed
The switch gear communications card
has been removed.
Refer to Module Replacement section
for further details.
Internal DC Disconnect
Switch Tripped
The internal DC disconnect switch
tripped and battery power is not avail-
able.
Activate the internal DC disconnect
switch.
Static Bypass Switch
Module Fault
A Static Bypass Switch module has
failed.
Contact APC Customer Support. See
Customer Support section.
Display message Meaning Corrective action