150 kW InfraStruXure Power Distribution Unit 21
Connect User Input Contacts and Relay
Outputs to the User Connection Plate
Overview
Make contact closure connections
(NO or NC) at the user connection
plate to monitor dry contacts. You
can make up to eight
connections—four input contacts
and four relay outputs.
The figure on the right shows the
location of the user connection
plate on the roof of the PDU
enclosure.
You can make connections from
inside the enclosure, or you can
remove the user connection plate to
make your connections.
Remove the plate using a Phillips
or standard screwdriver to loosen
the two captive screws. Use the
knockout in the plate to route
cables to and from the user
connections on the plate. If
removing the plate, make sure you
do not disturb the existing
connections.
1 234
ATS E N
ATS 0
AT S 1
ATS 2
EPO
Contact
– +
EPO 24 V
AC/D C
Contact Inputs
Contact Outp uts
USER INTERFACE
© 2001 APC