Installation Procedures: Install Shielding Troughs, Shielding Partitions, and Cable Ladders
24 150 kW InfraStruXure Power Distribution Unit
Shielding partitions. Shielding partitions form the side wall of a trough. You can customize the
width of the trough for each row in your system by making it wider for rows carrying many data
cables and narrower for rows carrying fewer cables. There are two types of shielding partitions:
Cable ladders for overhead wiring across rows
After installing the shielding toughs and shielding partitions, install the cable ladders between rows
of enclosures. You can also run cable ladders across shielding troughs in the same row using the
hardware provided in the ladder kit.
Use the wide 12-inch (305 mm) cable ladders in instances where many power cables or data cables
will run between rows, and use the narrow 6-inch (152 mm) cable ladders in instances where fewer
power cables or data cables will run between rows.
The cable ladders are 116 inch (2946 mm) long. You can adjust the length of the cable ladders in the
following ways:
Cut off the ends with a hacksaw to shorten them.
Insert the connectors only partially into the side rails to extend them.
As the back wall, use a shielding partition that
contains an opening for routing data cables.
As the front wall, use a solid shielding partition to
hide data cables for a clean appearance.
See also
For more information on installing cable ladders, see the instruction sheet included with
the cable ladders.
Note
Do not change the spacing between rows or the length and position of the cable ladders
from the layout you planned with your APC representative. For overhead wiring, each
PDU power cable is provided at a pre-determined length. Changes to the physical
configuration of your system could cause some power cables to be too short or too long.