Shutdown Parameters
All of the following settings are available with Smart-UPS, Matrix-UPS,
Symmetra, and Symmetra 3-Phase UPS models. The Shutdown Behavior
Settings for a Silcon UPS uses only the Low-Battery Duration, Maximum
Shutdown Time, and Shutdown Delay settings.
In the control console, you use the Battery option in the
Configuration menu to access the Return Battery
Capacity setting.
Action Definition
Return Battery
Capacity
Defines the minimum battery capacity that must be present
before the
UPS turns on after a shutdown that was caused by a
power failure.
Note:The
UPS must also wait until the time defined by the
Return Delay setting expires before it can turn on.
Low-Battery Duration
Defines how the
UPS can continue to run on battery once a low-
battery condition occurs.
Note: This setting also defines how much time PowerChute has
to safely shut down its server in response to the Turn
UPS Off Gracefully, Reboot Gracefully, and Put UPS
To Sleep Gracefully Control menu options.
Maximum Shutdown
Time (Web interface
only)
Reports the delay that is defined by the Maximum Shutdown
Time setting for the PowerChute network shutdown feature.
Note: For information about the PowerChute network shutdown
feature, see PowerChute® (UPS PowerChute network
shutdown); for information about how the Maximum
Shutdown Time is determined, see Maximum-
Shutdown-Time negotiation.
Shutdown Delay
Defines how long the
UPS will wait before it shuts down in
response to a turn-off command.