18 InfraStruXure InRow RC—Operation and Maintenance
View Status Readings
The display interface has several options for viewing the status of the cooling group, its cooling units,
and the environment being controlled. The status readings for cooling units are available under the
View Unit Status menu, and status readings for the cooling group are available under the View
Group Status menu or on the scrolling status screens.
Scrolling status screens
When the display interface is idle, it scrolls through screens of status information. Press the up or
down arrow key to interrupt the automatic scrolling and view a specific status screen.
Cooling unit status
Path: Main > View Unit Status
The cooling unit status screens contain information for each
cooling unit in a cooling group.
Op Mode. The cooling unit is either On, in Idle mode, or in
Standby mode.
Cool Output. The actual cooling output of the cooling unit.
Cool Demand. The amount of cooling that the rack currently
requires.
Supply Air. The temperature of the air leaving the cooling unit.
Return Air. The temperature of the air entering the cooling unit.
Rack Inlet. The air entering the rack at the temperature sensor.
Power Source. The source of power to the cooling unit.
Fluid In. The temperature of the chilled water as it enters the
cooling coil.
Fluid Out. The temperature of the chilled water as it leaves the
cooling coil.
Fluid Flow. The amount of chilled water, measured in gallons per minute or in liters per second, that
flows through the cooling unit.
Fluid Vlv Pos. The position of the valve that controls how much chilled water enters the cooling
unit.
Air Flow. The amount of air, in cubic feet per minute or in cubic meters per hour, required to
maintain the setpoint temperature.
Contain DP. The difference between the air pressure of the supply air entering the containment
system (RACS/HACS) and the air pressure of the return air leaving the containment system,
measured in inches water column.
On/Standby
View Alarms
Clear Alarms
View Event Log
na1637a
Clear Event Log
Configure Modbus
Set Date & Time
Set Password
Set Display Units
Configure Display
Configure Network
About InRow RC
Set Identification
Service Intervals
View Run Hours
Configure Unit
Configure Group
Set Group PID
View Group Status
View Unit Status
Set Group Setpoints
Set Unit Thresholds