APC ACRC301S User's Guide Page 46

  • Download
  • Add to my manuals
  • Print
  • Page
    / 60
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 45
Maintenance: Monthly Preventive Maintenance
40 InfraStruXure InRow RC—Operation and Maintenance
Mechanical
Check the fans. All components should be moving freely with no signs of binding or damages.
Verify that the condensate line is flowing freely.
Verify the chilled water supply temperature for cooling unit.
Chilled water supply temperature________________________
Electrical
Before checking the electrical connections shut off and lock out the power to the cooling unit.
Inspect the electrical panel for tight connections and overheated connections from loose contact
terminals.
Confirm the incoming main power matches the requirement’s listed on the cooling unit’s nameplate.
The measurement should be within 10% of the nameplate listing.
Page view 45
1 2 ... 41 42 43 44 45 46 47 48 49 50 51 ... 59 60

Comments to this Manuals

No comments