InfraStruXure InRow RC—Operation and Maintenance 21
Respond to Alarms
When an alarm is triggered, the cooling unit alerts you through the display by the following methods:
Alarm indicator on the scrolling status screen
LEDs on the front panel display
View alarms
Path: Main > View Alarms
The Alarms indicator appears on the scrolling status screens. It
provides the number of alarms, the severity, and a brief description
of the alarm. Press the arrow keys to view the rest of the list.
Clear alarms
Path: Main > Clear Alarms
Clear all active alarms. If the conditions that caused the alarm still exist, those conditions cause the
alarm to be regenerated.
See “View event log” on page 20 for more
information on the alarm/event details screens.
On/Standby
View Alarms
Clear Alarms
View Event Log
na1641a
Clear Event Log
Configure Modbus
Set Date & Time
Set Password
Set Display Units
Configure Display
Configure Network
About InRow RC
Set Identification
Service Intervals
View Run Hours
Configure Unit
Configure Group
Set Group PID
View Group Status
View Unit Status
Set Group Setpoints
Set Unit Thresholds