8
[mcontrol]
The following table describes the one OID in the [mcontrol] category. Value (3), not documented, is
obsolete.
[mconfig]
The following table describes the [mconfig] OIDs.
See How To Define Trap Receivers in Chapter 9, PowerNet MIB Traps for information on how to
define trap receivers.
OID Values You Can SET
mcontrolRestartAgent restartCurrentAgent (1): Reboots the SNMP Agent.
continueCurrentAgent (2): Continues the Agent without rebooting.
restartWithoutAgent (4): Restarts the system without starting the Agent.
The next time the system restarts, the Agent also restarts.
OID Task
mconfigBOOTPEnabled Identify the current BOOTP setting. A GET to this OID returns
one of the following:
yes (1): Enable BOOTP. The hardware device will obtain its IP
configuration parameters from a BOOTP server.
no (2): Disable BOOTP. The hardware device will use the IP
configuration parameters stored in its EPROM.
mconfigNumTrapReceivers Identify how many NMSs can receive traps from the Agent. A
GET to this OID returns a value from 0 to 4.
{mconfigTrapReceiverTable}
{mconfigTrapReceiverEntry}
trapIndex
receiverAddr
communityString
severity
acceptThisReceiver
receiveTrapType
Use this tabled set of OIDs to define up to four NMSs as trap
receivers. See How To Define Trap Receivers in Chapter 9,
PowerNet MIB Traps for information on the OIDs in this table.
mconfigClock Configure the date and time on a Web/SNMP Management Card,
Network Management Card, or MasterSwitch unit.
mconfigClockDate in mm/dd/yyyy format
mconfigClockTime in hh:mm:ss am/pm format