Chapter 7:
[sPDUOutletStatusMSP] Outlet Status OIDs
PowerNet MIB Reference Guide
63
[sPDUOutletStatusMSP] Outlet Status OIDs
The [sPDUOutletStatusMSP] category has a tabled set of OIDS that provides information on the status of the outlets
for MasterSwitch Plus unit.
OID Information Provided
{sPDUOutletStatusMSPTable}
{sPDUOutletStatusMSPEntry}
sPDUOutletStatusMSPIndex
sPDUOutletStatusMSPName
sPDUOutletStatusMSPOutletIndex
sPDUOutletStatusMSPOutletName
sPDUOutletStatusMSPOutletState
sPDUOutletStatusMSPCommandPending
sPDUOutletStatusMSPOutletCtrlMode
View status information for a specified outlet. (The
sPDUMasterStatusMSPOutletCount OID identifies the number
of table entries.)
• The index to the MasterSwitch Plus unit’s entry (read only).
• The name of the MasterSwitch Plus unit (read only). (You use
the sPDUMasterConfigMSPName OID to define this name).
• The outlet number (read only)
• The name of the outlet (read only). (You use the
sPDUOutletConfigMSPallOutletName OID to define this
name).
• One of the following:
- outletStatusOnMSP (1) if the outlet is on
- outletStatusOffMSP (2) if the outlet is off
• One of the following:
- outletStatusMSPCommandPending (1) if a command is
pending on the outlet.
- outletStatusMSPNoCommandPending (2) if no command
is pending on the outlet.
• The control mode of the outlet, as defined by the OID
sPDUOutletConfigMSPallOutletCtrlMode:
- modeGracefulShutdown: (1): In Graceful Shutdown control
mode, the outlet turns off after a server supported by the UPS
has completed a graceful shutdown.
- modeAnnunciator (2): In Annunciator control mode, the
outlet turns off in response to an environmental alarm from an
Environmental Monitor and turns on when the cause is
resolved.