Chapter 3:
How to Control a UPS
PowerNet MIB Reference Guide
19
upsAdvControlUpsSleep Cause the UPS to turn off its outlets and wait in “sleep mode”
for the period of time defined by
upsAdvConfigUpsSleepTime, a UPS configuration OID (See
How to Configure a UPS.)
• noPutUpsToSleep (1): The value always returned for a
GET. Setting this value has no effect.
• putUpsToSleep (2): All Management Cards turn off UPS
power immediately.
• putUpsToSleepGracefully (3): A Management Card turns
off UPS power after a delay defined by
upsAdvConfigShutoffDelay, a UPS configuration OID.
(See How to Configure a UPS.)
upsAdvControlSimulatePowerFail Cause the UPS to test its ability to switch to battery operation
as it would in a power failure:
• noSimulatePowerFailure (1): The value always returned
for a GET. Setting this value has no effect.
• simulatePowerFailure (2): The UPS performs this test.
upsAdvControlFlashAndBeep Cause the UPS to test its front panel lights (if any) and its
audible alarm:
• noFlashAnd Beep (1): The value always returned for a
GET. Setting this value has no effect.
• flashAndBeep (2): The UPS performs this test.
upsAdvControlTurnOnUPS Cause a Management Card’s UPS to turn on:
• noTurnOnUPS (1): The value always returned for a GET.
Setting this value has no effect.
• turnOnUPS (2): The UPS turns on, if that UPS was turned
off using the upsAdvControlUpsOff OID.
upsAdvControlBypassSwitch Switch a Matrix-UPS or Symmetra UPS to or from software
bypass mode:
• noBypassSwitch (1): The value always returned for a GET.
Setting this value has no effect.
• switchToBypass (2): The UPS switches to bypass mode.
• switchOutOfBypass (3): The UPS switches from bypass
mode to normal operation.
OID Task (page 2 of 2)