APC AP9212 Technical Information Page 89

  • Download
  • Add to my manuals
  • Print
  • Page
    / 95
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 88
Chapter 9:
PowerNet MIB Trap Definitions
PowerNet MIB Reference Guide
82
dcMajorAlarm Severe 113: A Major alarm is active in the DC power
plant.
dcMajorAlarmCleared Informational 114: A Major alarm is no longer active in the DC
power plant.
dcMinorAlarm Severe 115: A Minor alarm is active in the DC power
plant.
dcMinorAlarmCleared Informational 116: A Minor alarm is no longer active in the DC
power plant.
dcOutputRelayOn Warning 117: An output relay has gone on in the DC power
plant.
dcOutputRelayOff Informational 118: An input relay has gone off in the DC power
plant.
dcIntputRelayOn Warning 119: An input relay has gone on in the DC power
plant.
dcIntputRelayOff Informational 120: An output relay has gone off in the DC power
plant.
logicPowerSuppliesIncreased Informational 121: The number of logic power supplies has
increased at the Symmetra 3-Phase UPS.
logicPowerSuppliesDecreased Informational 122: The number of logic power supplies has
decreased at the Symmetra 3-Phase UPS.
externalSwitchGearClosed Informational 123: The identified external switch gear at the
Symmetra 3-Phase UPS is closed.
externalSwitchGearOpened Informational 124: The identified external switch gear at the
Symmetra 3-Phase UPS is open
generalDeviceEvent Informational 125: The identified general event occurred at the
Symmetra 3-Phase UPS.
atsSourceSwitched Informational 126: The Automatic Transfer Switch has switched
source.
atsLostRedundancy Severe 127: The Automatic Transfer Switch has lost
redundancy.
atsRedundancyRestored Informational 128: Redundancy has been restored to the
Automatic Transfer Switch.
atsConfigChange Informational 129: A configuration change has been made on a
Automatic Transfer Switch.
atsCommunicationEstablished Informational 130: Communications with the Automatic Transfer
Switch has been established.
atsCommunicationLost Severe 131: Communications with the Automatic Transfer
Switch has been lost.
atsOverCurrent Severe 132: Output Current of the Automatic Transfer
Switch has exceeded threshold.