APC AP9212 Technical Information Page 42

  • Download
  • Add to my manuals
  • Print
  • Page
    / 95
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 41
Chapter 4:
Measure-UPS (mUps) OIDs
PowerNet MIB Reference Guide
35
[iemStatusContacts] OIDs
You use the following [iemStatusContacts] read-only OIDs to view information about the input
contacts at an Integrated Environmental Monitor.
[iemStatusRelays] OIDs
You use the following [iemStatusRelays] read-only OIDs to view information about the output relay
associated with the Integrated Environmental Monitor.
Measure-UPS (mUps) OIDs
Two categories of mUps OIDs provide for managing external Environmental Monitors through a
Management Card or PowerNet Agent that uses a previous version of the PowerNet MIB.
[mUpsEnviron] Environment OIDs
[mUpsContact] Contact OIDS
To access these mUps OIDs in the PowerNet MIB, do the following:
1. Select [products] under [apc].
2. Select [hardware].
3. Select [measureUps].
OID Information Reported
iemStatusContactsNumContacts The number of available contacts
{iemStatusContactsTable}
{iemStatusContactsEntry}
iemStatusContactNumber
iemStatusContactName
iemStatusContactStatus
Access the set of OIDs for each input contact and view
the following information:
The number of the contact
The name of the contact
The noFault (1), fault (2), or disabled (3) status
OID Information Reported
iemStatusRelaysNumRelays The number of available output relays
{iemStatusRelaysTable}
{iemStatusRelaysEntry}
iemStatusRelayNumber
iemStatusRelayName
iemStatusRelaytStatus
Access the set of OIDs for each output relay and view
the following information:
The number of the output relay
The name of the output relay
The faultState (1) or normalState (2) status
Page view 41
1 2 ... 37 38 39 40 41 42 43 44 45 46 47 ... 94 95

Comments to this Manuals

No comments