APC AP9212 Technical Information Page 22

  • Download
  • Add to my manuals
  • Print
  • Page
    / 95
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 21
Chapter 3:
How to Monitor a UPS
PowerNet MIB Reference Guide
15
[upsAdvInput]
See How to Configure a UPS for information about the following values mentioned in the
descriptions of [upsAdvLineFailCause] OID values in the preceding table:
Rated output of the UPS
The high-transfer voltage value
The low-transfer voltage value
OID Information Reported
upsAdvInputLineVoltage The current input voltage in VAC.
upsAdvInputMaxLineVoltage The maximum input voltage, in VAC, sensed by the UPS during
the last minute.
upsAdvInputMinLineVoltage The minimum input voltage, in VAC, sensed by the UPS during
the last minute.
upsAdvInputFrequency The current input voltage frequency in Hertz.
upsAdvLineFailCause The reason for the most recent transfer to battery.
Any Management Card or smart-signalling PowerNet Agent can
report the following:
- noTransfer (1): No transfer has occurred.
- highLineVoltage (2): Voltage exceeded the high-transfer
voltage value.
- brownout (3): For more than 5 seconds, the voltage level was
between 40% of the UPS rated output voltage and the low-
transfer voltage value.
- blackout (4): For more than 5 seconds, the voltage level was
between 40% of the UPS rated output voltage and ground [0
volts].
- smallMomentarySag (5): A brownout existed for 5 seconds
or less.
- deepMomentarySag (6): A blackout existed for 5 seconds or
less.
- smallMomentarySpike (7): Less than 10 volts per cycle
voltage increase.
- largeMomentarySpike (8): More than 10 volts per cycle
voltage increase.
A Management Card can also report the occurrence of a UPS
self-test, self-test (9), and the rate of changes in the line voltage
level, rateOfVoltageChange (10).