Chapter 5:
[sPDUMasterControl] Master Control OIDs
PowerNet MIB Reference Guide
39
[sPDUMasterControl] Master Control OIDs
The [sPDUMasterControl] category has two OIDs that respond to GETs with information about all eight outlets and a
third OID that uses SETs to directly affect the operation of all outlets simultaneously.
OID Task
sPDUMasterControlSwitch
Affect the operation of all outlets.
turnAllOnNow (1): Immediately turn on all outlets.
turnAllOnSequence (2): Turn on all outlets by using the
sPDUOutletPowerOnTime OID value for each outlet.
turnAllOffNow (3): Immediately turn off all outlets.
rebootAllNow (4): Immediately reboot all outlets by turning off power and then
turning on power based on the master powers sPDUMasterConfigReboot
configuration OID value.
rebootAllSequence (5):
- For firmware version 2.x: Turn off all outlets as described for
turnAllOffSequence, wait the delay time specified as
sPDUMasterConfigReboot, and then turn on all outlets as described for
turnAllOnSequence.
- For firmware version 1.x: Reboot all outlets as described for
turnAllOnSequence.
noCommand (6): The value returned for a GET.
turnAllOffSequence (7): Turn off all outlets by using each outlets
sPDUOutletPowerOffTime configuration OID value.
Note: The turnAllOffSequence (7) setting has no effect when used with
firmware version 1.x.
sPDUMasterState
Identify the on or off status of the eight outlets.
sPDUMasterPending
Identify whether any outlet has a command pending (yes or no).
For information on [sPDUMasterConfigReboot] and [sPDUMasterConfigPowerOn], see [sPDUMasterConfig] Master
Configuration OIDs; for information on [sPDUMasterConfigReboot] and [sPDUOutletPowerOnTime] OIDs, see
[sPDUOutletConfig] Outlet Configuration OIDs.