Chapter 7:
[sPDUMasterConfigMSP] Master Configuration OIDs
PowerNet MIB Reference Guide
54
[sPDUMasterConfigMSP] Master Configuration OIDs
The [sPDUMasterConfigMSP] category has a read-only OID and a tabled set of OIDS that provide commands to
configure the MasterSwitch Plus unit.
[sPDUMasterStatusMSP] Master Status OIDs
The [sPDUMasterStatusMSP] category has one read-only OID and a tabled set of read-only OIDs that provide
information on the status of the MasterSwitch Plus unit.
OID Task
sPDUMasterConfigMSPTableSize The number of MasterSwitch Plus units.
{sPDUMasterConfigMSPTable}
{sPDUMasterConfigMSPEntry}
sPDUMasterConfigMSPindex
sPDUMasterConfigMSPName
sPDUMasterConfigMSPPowerOnTimeDelay
sPDUMasterConfigMSPManualButton
View and configure a specified MasterSwitch Plus unit.
• The index to the MasterSwitch Plus unit’s entry ( read-only).
• Define a name (up to 23 characters) for the MasterSwitch Plus
unit.
• Define the delay that will occur from the time that power is
applied to the MasterSwitch Plus unit until the it supplies basic
master power to its outlets:
- 0: Begin providing output power immediately.
- 1 throug 9999 seconds (2 hours, 46 minutes, 39 seconds):
Provide output power after the specified delay.
• Disable (manualButtonDisabled (1)) or enable
manualButtonEnabled (2) the manual button on the
MasterSwitch Plus unit.
OID Information Reported
sPDUMasterStatusMSPTableSize The number of MasterSwitch Plus units.
{sPDUMasterStatusMSPTable}
{sPDUMasterStatusMSPEntry}
sPDUMasterStatusMSPIndex
sPDUMasterStatusMSPName
sPDUMasterStatusMSPOutletCount
View identification information about a specified MasterSwitch Plus
unit.
• The index to the MasterSwitch Plus unit’s entry (read only).
• The name of the MasterSwitch Plus unit (read only) (You use the
sPDUMasterConfigMSPName OID to define this name).
• The number of MasterSwitch Plus outlets.