Chapter 9:
Symmetra UPS Subtraps
PowerNet MIB Reference Guide
85
Symmetra UPS Subtraps
The abnormalCondition and abnormalConditionCleared traps for the Symmetra UPS have the
following subtraps that identify the abnormal condition.
Note:
To make the MIB forward-compatible with future UPS models, subtraps 41
through 64 are defined but unused at the time this manual is being published.
If you use a new UPS model that was released after the publication of this
manual, you could receive a subtrap for one of these subtrap numbers even if
you have not upgraded the firmware for your Management Card. If this
occurs, contact APC to obtain the latest MIB and TDF files, which will
describe the newly defined bit.
Subtrap Description (Sheet 1 of 3)
SYMtrapstr1 An installed power module has failed.
SYMtrapstr2 A failed power module condition has been corrected.
SYMtrapstr3 An installed intelligence module has failed.
SYMtrapstr4 A failed intelligence module condition has been corrected.
SYMtrapstr5 An installed redundant intelligence module has failed.
SYMtrapstr6 A failed redundant intelligence module condition has been corrected.
SYMtrapstr7 An installed battery has failed.
SYMtrapstr8 A failed battery condition has been corrected.
SYMtrapstr9 The load is above the alarm threshold.
SYMtrapstr10 The violation of the load alarm threshold has been corrected.
SYMtrapstr11 The UPS has lost its redundancy.
SYMtrapstr12 The loss of redundancy has been corrected.
SYMtrapstr13 The redundancy of the UPS is at or below the alarm threshold.
SYMtrapstr14 The redundancy of the UPS is above the alarm threshold again.
SYMtrapstr15 The UPS is on bypass because input voltage and frequency were out of range.
SYMtrapstr16 Input voltage and frequency are back in range. so the UPS returned from bypass.
SYMtrapstr17 The bypass contactor is stuck in bypass position.
SYMtrapstr18 The bypass contactor is no longer stuck in bypass position.
SYMtrapstr19 The bypass contactor is stuck in the on-line position.