Chapter 4:
External Environmental Monitor (em) OIDs
PowerNet MIB Reference Guide
31
[emStatusProbes] OIDs
You use the following [emStatusProbes] read-only OIDs to view information about the temperature
and humidity probes at an external Environmental Monitor.
[emStatusContacts] OIDs
You use the following [emStatusContacts] read-only OIDs to view information about the input
contacts at an external Environmental Monitor.
OID Information Reported
emStatusProbesNumProbes The number of available probes
{emStatusProbesTable}
{emStatusProbesEntry}
emStatusProbeNumber
emStatusProbeName
emStatusProbeStatus
emStatusProbeCurrentTemp
emStatusProbeTempUnits
emStatusProbeCurrentHumid
emStatusProbeHighTempViolation
emStatusProbeLowTempViolation
emStatusProbeHighHumidViolation
emStatusProbeLowHumidViolation
Access the set of OIDs for each input contact and view
the following information:
The number of the probe
The name of the probe
The disconnected (1) or connected (2) status of the
probe
The current temperature reading at the probe
Whether Celsius (1) or Fahrenheit (2) temperature
values are used by the probe
Note:
The temperature unit is defined by a system
preferences setting at the agent.
The current humidity reading at the probe
The noViolation (1), highTempViolation (2), or
disabled (3) status of the high-temperature alarm
The noViolation (1), lowTempViolation (2), or
disabled (3) status of the low-temperature alarm
The noViolation (1), highHumidViolation (2), or
disabled (3) status of the high-humidity alarm
The noViolation (1), lowHumidViolation (2), or
disabled (3) status of the low-humidity alarm
OID Information Reported
emStatusContactsNumContacts The number of available contacts
{emStatusContactsTable}
{emStatusContactsEntry}
emStatusContactNumber
emStatusContactName
emStatusContactStatus
Access the set of OIDs for each input contact and view
the following information:
The number of the contact
The name of the contact
The noFault (1), fault (2), or disabled (3) status of
the contact alarm